6500 kcmil THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 80

11.258 sq in × 40 % = 4.5032 sq in allowed. ÷ 0.7073 sq in per wire = 6.37, so 6.

6 500 kcmil THHN in 4" PVC Sch 80, drawn to scale

This pull in numbers

6 wires fill
37.7 % of 4" PVC Sch 80
Limit for three or more
40 %
For 7 or more
5" PVC Sch 80, up to 10
Pipe to wire diameter
3.99 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit

Before you pull 6

500 kcmil THHN in other 4" conduit

500 kcmil THHN in other PVC Sch 80 sizes

Other wire sizes in 4" PVC Sch 80