ConduitCount

How many 500 kcmil THHN fit in 3-1/2" PVC Sch 40?

5500 kcmil THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 40

9.737 sq in × 40 % = 3.8948 sq in allowed. ÷ 0.7073 sq in per wire = 5.51, so 5.

5 500 kcmil THHN in 3-1/2" PVC Sch 40, drawn to scale

This pull in numbers

5 wires fill
36.3 % of 3-1/2" PVC Sch 40
Limit for three or more
40 %
For 6 or more
4" PVC Sch 40, up to 7
Pipe to wire diameter
3.71 to 1
In THW insulation
5 fit
In XHHW-2 insulation
5 fit

Before you pull 5

500 kcmil THHN in other 3-1/2" conduit

500 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 3-1/2" PVC Sch 40