ConduitCount

How many 500 kcmil THHN fit in 6" PVC Sch 40?

16500 kcmil THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 40

28.567 sq in × 40 % = 11.4268 sq in allowed. ÷ 0.7073 sq in per wire = 16.16, so 16.

16 500 kcmil THHN in 6" PVC Sch 40, drawn to scale

This pull in numbers

16 wires fill
39.6 % of 6" PVC Sch 40
Limit for three or more
40 %
For 17 or more
no bigger PVC Sch 40
Pipe to wire diameter
6.36 to 1
In THW insulation
14 fit
In XHHW-2 insulation
16 fit

Before you pull 16

500 kcmil THHN in other 6" conduit

ConduitInside areaMost 500 kcmil THHN
Rigid metal conduit (RMC, GRC)29.15816
Rigid PVC conduit, Schedule 4028.56716
Rigid PVC conduit, Schedule 8025.59814

500 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 6" PVC Sch 40

Charts