ConduitCount

How many 500 kcmil THHN fit in 1-1/4" PVC Sch 40?

1500 kcmil THHN/THWN-2 wires in 1-1/4" Rigid PVC conduit, Schedule 40

1.453 sq in × 53 % = 0.7701 sq in allowed. ÷ 0.7073 sq in per wire = 1.09.

1 500 kcmil THHN in 1-1/4" PVC Sch 40, drawn to scale

This pull in numbers

1 wires fill
48.7 % of 1-1/4" PVC Sch 40
Limit for one
53 %
For 2 or more
2-1/2" PVC Sch 40, up to 2
Pipe to wire diameter
1.43 to 1
In THW insulation
0 fit
In XHHW-2 insulation
1 fit

Before you pull 1

500 kcmil THHN in other 1-1/4" conduit

ConduitInside areaMost 500 kcmil THHN
Electrical metallic tubing1.4961
Intermediate metal conduit1.6471
Rigid metal conduit (RMC, GRC)1.5261
Rigid PVC conduit, Schedule 401.4531
Rigid PVC conduit, Schedule 801.2370
Flexible metal conduit (FMC, Greenfield)1.2770
Liquidtight flexible metal conduit (LFMC)1.5281
Electrical nonmetallic tubing (smurf tube)1.4531

500 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 1-1/4" PVC Sch 40

Charts