How many #6 THHN fit in 2" EMT?

266 AWG THHN/THWN-2 wires in 2" Electrical metallic tubing

3.356 sq in × 40 % = 1.3424 sq in allowed. ÷ 0.0507 sq in per wire = 26.48, so 26.

26 #6 THHN in 2" EMT, drawn to scale

This pull in numbers

26 wires fill
39.3 % of 2" EMT
Limit for three or more
40 %
For 27 or more
2-1/2" EMT, up to 46
Pipe to wire diameter
8.14 to 1
In THW insulation
18 fit
In XHHW-2 insulation
22 fit

Before you pull 26