ConduitCount

How many #6 THHN fit in 2" Rigid?

276 AWG THHN/THWN-2 wires in 2" Rigid metal conduit (RMC, GRC)

3.408 sq in × 40 % = 1.3632 sq in allowed. ÷ 0.0507 sq in per wire = 26.89, which Note 7 rounds up to 27 because the decimal is 0.8 or more.

27 #6 THHN in 2" Rigid, drawn to scale

This pull in numbers

27 wires fill
40.2 % of 2" Rigid
Limit for three or more
40 %
For 28 or more
2-1/2" Rigid, up to 38
Pipe to wire diameter
8.20 to 1
In THW insulation
18 fit
In XHHW-2 insulation
23 fit

Before you pull 27

#6 THHN in other 2" conduit

#6 THHN in other Rigid sizes

Other wire sizes in 2" Rigid

Charts