ConduitCount

How many #8 THHN fit in 1-1/2" Rigid?

228 AWG THHN/THWN-2 wires in 1-1/2" Rigid metal conduit (RMC, GRC)

2.071 sq in × 40 % = 0.8284 sq in allowed. ÷ 0.0366 sq in per wire = 22.63, so 22.

22 #8 THHN in 1-1/2" Rigid, drawn to scale

This pull in numbers

22 wires fill
38.9 % of 1-1/2" Rigid
Limit for three or more
40 %
For 23 or more
2" Rigid, up to 37
Pipe to wire diameter
7.52 to 1
In THW insulation
19 fit
In XHHW-2 insulation
19 fit

Before you pull 22

#8 THHN in other 1-1/2" conduit

#8 THHN in other Rigid sizes

Other wire sizes in 1-1/2" Rigid

Charts