ConduitCount

How many #8 THHN fit in 4" Rigid?

1408 AWG THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.0366 sq in per wire = 140.79, so 140.

140 #8 THHN in 4" Rigid, drawn to scale

This pull in numbers

140 wires fill
39.8 % of 4" Rigid
Limit for three or more
40 %
For 141 or more
5" Rigid, up to 221
Pipe to wire diameter
18.75 to 1
In THW insulation
118 fit
In XHHW-2 insulation
118 fit

Before you pull 140

#8 THHN in other 4" conduit

#8 THHN in other Rigid sizes

Other wire sizes in 4" Rigid

Charts