ConduitCount

How many #8 THHN fit in 2" Rigid?

378 AWG THHN/THWN-2 wires in 2" Rigid metal conduit (RMC, GRC)

3.408 sq in × 40 % = 1.3632 sq in allowed. ÷ 0.0366 sq in per wire = 37.25, so 37.

37 #8 THHN in 2" Rigid, drawn to scale

This pull in numbers

37 wires fill
39.7 % of 2" Rigid
Limit for three or more
40 %
For 38 or more
2-1/2" Rigid, up to 53
Pipe to wire diameter
9.64 to 1
In THW insulation
31 fit
In XHHW-2 insulation
31 fit

Before you pull 37

#8 THHN in other 2" conduit

#8 THHN in other Rigid sizes

Other wire sizes in 2" Rigid

Charts