How many #8 THHN fit in 4" IMC?

1498 AWG THHN/THWN-2 wires in 4" Intermediate metal conduit

13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.0366 sq in per wire = 148.97, which Note 7 rounds up to 149 because the decimal is 0.8 or more.

149 #8 THHN in 4" IMC, drawn to scale

This pull in numbers

149 wires fill
40.0 % of 4" IMC
Limit for three or more
40 %
For 150 or more
no bigger IMC
Pipe to wire diameter
19.29 to 1
In THW insulation
124 fit
In XHHW-2 insulation
124 fit

Before you pull 149

#8 THHN in other 4" conduit

#8 THHN in other IMC sizes

Other wire sizes in 4" IMC

Charts