ConduitCount

1-1/4" EMT conduit fill

1-1/4" Electrical metallic tubing has an inside area of 1.496 sq in (1.380 in across). Three or more wires may take 40 % of it: 0.5984 sq in.

One wire, 53 %
0.7929 sq in
Two wires, 31 %
0.4638 sq in
Three or more, 40 %
0.5984 sq in
Nipple, 60 %
0.8976 sq in
Support
Every 10 ft, 3 ft from boxes
Sold in
10 ft sticks
45 #12 THHN, the most it may hold, drawn to scale

How many wires fit in 1-1/4" EMT

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG614343
12 AWG453333
10 AWG282424
8 AWG161313
6 AWG12108
4 AWG776
3 AWG665
2 AWG554
1 AWG443
1/0 AWG332
2/0 AWG221
3/0 AWG111
4/0 AWG111
250 kcmil111
300 kcmil111
350 kcmil111
400 kcmil111
500 kcmil111

Other 1-1/4" conduit

ConduitInside area#14#12#10#8#6
Electrical metallic tubing1.4966145281612
Intermediate metal conduit1.6476849311813
Rigid metal conduit (RMC, GRC)1.5266346291612
Rigid PVC conduit, Schedule 401.4536043271611
Rigid PVC conduit, Schedule 801.237513723139
Flexible metal conduit (FMC, Greenfield)1.2775238241410
Liquidtight flexible metal conduit (LFMC)1.5286346291612
Electrical nonmetallic tubing (smurf tube)1.4536043271611

About EMT

EMT is the thin-wall steel tubing most commercial work uses. It is strapped within 3 ft of each box and every 10 ft (358.30), and joined with set-screw or compression couplings. See strap spacing and the fill rules.