How many #1/0 THHN fit in 1-1/4" EMT?

31/0 AWG THHN/THWN-2 wires in 1-1/4" Electrical metallic tubing

1.496 sq in × 40 % = 0.5984 sq in allowed. ÷ 0.1855 sq in per wire = 3.23, so 3.

3 #1/0 THHN in 1-1/4" EMT, drawn to scale

This pull in numbers

3 wires fill
37.2 % of 1-1/4" EMT
Limit for three or more
40 %
For 4 or more
1-1/2" EMT, up to 4
Pipe to wire diameter
2.84 to 1
In THW insulation
2 fit
In XHHW-2 insulation
3 fit

The pipe is 2.84 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.