ConduitCount

How many #2 THHN fit in 1-1/4" EMT?

52 AWG THHN/THWN-2 wires in 1-1/4" Electrical metallic tubing

1.496 sq in × 40 % = 0.5984 sq in allowed. ÷ 0.1158 sq in per wire = 5.17, so 5.

5 #2 THHN in 1-1/4" EMT, drawn to scale

This pull in numbers

5 wires fill
38.7 % of 1-1/4" EMT
Limit for three or more
40 %
For 6 or more
1-1/2" EMT, up to 7
Pipe to wire diameter
3.59 to 1
In THW insulation
4 fit
In XHHW-2 insulation
5 fit

Before you pull 5

#2 THHN in other 1-1/4" conduit

#2 THHN in other EMT sizes

Other wire sizes in 1-1/4" EMT

Charts