How many #1 THHN fit in 1-1/4" EMT?

41 AWG THHN/THWN-2 wires in 1-1/4" Electrical metallic tubing

1.496 sq in × 40 % = 0.5984 sq in allowed. ÷ 0.1562 sq in per wire = 3.83, which Note 7 rounds up to 4 because the decimal is 0.8 or more.

4 #1 THHN in 1-1/4" EMT, drawn to scale

This pull in numbers

4 wires fill
41.8 % of 1-1/4" EMT
Limit for three or more
40 %
For 5 or more
1-1/2" EMT, up to 5
Pipe to wire diameter
3.09 to 1
In THW insulation
3 fit
In XHHW-2 insulation
4 fit

The pipe is 3.09 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.