ConduitCount

How many #3 THHN fit in 1-1/4" EMT?

63 AWG THHN/THWN-2 wires in 1-1/4" Electrical metallic tubing

1.496 sq in × 40 % = 0.5984 sq in allowed. ÷ 0.0973 sq in per wire = 6.15, so 6.

6 #3 THHN in 1-1/4" EMT, drawn to scale

This pull in numbers

6 wires fill
39.0 % of 1-1/4" EMT
Limit for three or more
40 %
For 7 or more
1-1/2" EMT, up to 8
Pipe to wire diameter
3.92 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit

Before you pull 6

#3 THHN in other 1-1/4" conduit

#3 THHN in other EMT sizes

Other wire sizes in 1-1/4" EMT

Charts