ConduitCount

2-1/2" PVC Sch 40 conduit fill

2-1/2" Rigid PVC conduit, Schedule 40 has an inside area of 4.695 sq in (2.445 in across). Three or more wires may take 40 % of it: 1.8780 sq in.

One wire, 53 %
2.4884 sq in
Two wires, 31 %
1.4555 sq in
Three or more, 40 %
1.8780 sq in
Nipple, 60 %
2.8170 sq in
Support
Every 6 ft, 3 ft from boxes
Sold in
10 ft sticks
51 #8 THHN, the most it may hold, drawn to scale

How many wires fit in 2-1/2" PVC Sch 40

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG193135135
12 AWG141103103
10 AWG897777
8 AWG514343
6 AWG373226
4 AWG222319
3 AWG191916
2 AWG161614
1 AWG121210
1/0 AWG10108
2/0 AWG887
3/0 AWG776
4/0 AWG665
250 kcmil454
300 kcmil443
350 kcmil333
400 kcmil333
500 kcmil221
600 kcmil111
700 kcmil111
750 kcmil111
800 kcmil111
900 kcmil111
1000 kcmil111

Other 2-1/2" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 404.695193141895137
Electrical metallic tubing5.8582411761116446
Intermediate metal conduit5.135211154975640
Rigid metal conduit (RMC, GRC)4.866200146925338
Rigid PVC conduit, Schedule 804.119170124784532
Flexible metal conduit (FMC, Greenfield)4.909202147935338
Liquidtight flexible metal conduit (LFMC)4.881201146925338

About PVC Sch 40

Schedule 40 is the standard PVC wall. Support spacing gets wider as the size goes up (Table 352.30), and long runs in the sun need expansion fittings (352.44). See strap spacing and the fill rules.