ConduitCount

How many #1/0 THHN fit in 2-1/2" PVC Sch 40?

101/0 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 40

4.695 sq in × 40 % = 1.8780 sq in allowed. ÷ 0.1855 sq in per wire = 10.12, so 10.

10 #1/0 THHN in 2-1/2" PVC Sch 40, drawn to scale

This pull in numbers

10 wires fill
39.5 % of 2-1/2" PVC Sch 40
Limit for three or more
40 %
For 11 or more
3" PVC Sch 40, up to 15
Pipe to wire diameter
5.03 to 1
In THW insulation
8 fit
In XHHW-2 insulation
10 fit

Before you pull 10

#1/0 THHN in other 2-1/2" conduit

#1/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 2-1/2" PVC Sch 40

Charts