2-1/2" PVC Sch 80 conduit fill

2-1/2" Rigid PVC conduit, Schedule 80 has an inside area of 4.119 sq in (2.290 in across). Three or more wires may take 40 % of it: 1.6476 sq in.

One wire, 53 %
2.1831 sq in
Two wires, 31 %
1.2769 sq in
Three or more, 40 %
1.6476 sq in
Nipple, 60 %
2.4714 sq in
Support
Every 6 ft, 3 ft from boxes
Sold in
10 ft sticks
45 #8 THHN, the most it may hold, drawn to scale

How many wires fit in 2-1/2" PVC Sch 80

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG170118118
12 AWG1249191
10 AWG786868
8 AWG453737
6 AWG322822
4 AWG202017
3 AWG171714
2 AWG141412
1 AWG10108
1/0 AWG997
2/0 AWG776
3/0 AWG665
4/0 AWG554
250 kcmil443
300 kcmil333
350 kcmil332
400 kcmil331
500 kcmil111
600 kcmil111
700 kcmil111
750 kcmil111
800 kcmil111
900 kcmil111
1000 kcmil111

Other 2-1/2" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 804.119170124784532
Electrical metallic tubing5.8582411761116446
Intermediate metal conduit5.135211154975640
Rigid metal conduit (RMC, GRC)4.866200146925338
Rigid PVC conduit, Schedule 404.695193141895137
Flexible metal conduit (FMC, Greenfield)4.909202147935338
Liquidtight flexible metal conduit (LFMC)4.881201146925338

About PVC Sch 80

Schedule 80 has a thicker wall for where it can be hit, so it holds fewer wires than Schedule 40 of the same trade size. Support is the same as Schedule 40 (Table 352.30). See strap spacing and the fill rules.