ConduitCount

How many #8 THHN fit in 2-1/2" PVC Sch 40?

518 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 40

4.695 sq in × 40 % = 1.8780 sq in allowed. ÷ 0.0366 sq in per wire = 51.31, so 51.

51 #8 THHN in 2-1/2" PVC Sch 40, drawn to scale

This pull in numbers

51 wires fill
39.8 % of 2-1/2" PVC Sch 40
Limit for three or more
40 %
For 52 or more
3" PVC Sch 40, up to 79
Pipe to wire diameter
11.32 to 1
In THW insulation
43 fit
In XHHW-2 insulation
43 fit

Before you pull 51

#8 THHN in other 2-1/2" conduit

#8 THHN in other PVC Sch 40 sizes

Other wire sizes in 2-1/2" PVC Sch 40

Charts