ConduitCount

How many #2/0 THHN fit in 2-1/2" PVC Sch 40?

82/0 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 40

4.695 sq in × 40 % = 1.8780 sq in allowed. ÷ 0.2223 sq in per wire = 8.45, so 8.

8 #2/0 THHN in 2-1/2" PVC Sch 40, drawn to scale

This pull in numbers

8 wires fill
37.9 % of 2-1/2" PVC Sch 40
Limit for three or more
40 %
For 9 or more
3" PVC Sch 40, up to 13
Pipe to wire diameter
4.60 to 1
In THW insulation
7 fit
In XHHW-2 insulation
8 fit

Before you pull 8

#2/0 THHN in other 2-1/2" conduit

#2/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 2-1/2" PVC Sch 40

Charts