ConduitCount

How many #2 THHN fit in 2-1/2" PVC Sch 40?

162 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 40

4.695 sq in × 40 % = 1.8780 sq in allowed. ÷ 0.1158 sq in per wire = 16.22, so 16.

16 #2 THHN in 2-1/2" PVC Sch 40, drawn to scale

This pull in numbers

16 wires fill
39.5 % of 2-1/2" PVC Sch 40
Limit for three or more
40 %
For 17 or more
3" PVC Sch 40, up to 25
Pipe to wire diameter
6.37 to 1
In THW insulation
14 fit
In XHHW-2 insulation
16 fit

Before you pull 16

#2 THHN in other 2-1/2" conduit

#2 THHN in other PVC Sch 40 sizes

Other wire sizes in 2-1/2" PVC Sch 40