ConduitCount

How many #3/0 THHN fit in 2-1/2" PVC Sch 40?

73/0 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 40

4.695 sq in × 40 % = 1.8780 sq in allowed. ÷ 0.2679 sq in per wire = 7.01, so 7.

7 #3/0 THHN in 2-1/2" PVC Sch 40, drawn to scale

This pull in numbers

7 wires fill
39.9 % of 2-1/2" PVC Sch 40
Limit for three or more
40 %
For 8 or more
3" PVC Sch 40, up to 11
Pipe to wire diameter
4.19 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 7

#3/0 THHN in other 2-1/2" conduit

#3/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 2-1/2" PVC Sch 40

Charts