ConduitCount

How many 300 kcmil THHN fit in 6" PVC Sch 40?

24300 kcmil THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 40

28.567 sq in × 40 % = 11.4268 sq in allowed. ÷ 0.4608 sq in per wire = 24.80, so 24.

24 300 kcmil THHN in 6" PVC Sch 40, drawn to scale

This pull in numbers

24 wires fill
38.7 % of 6" PVC Sch 40
Limit for three or more
40 %
For 25 or more
no bigger PVC Sch 40
Pipe to wire diameter
7.87 to 1
In THW insulation
21 fit
In XHHW-2 insulation
25 fit

Before you pull 24

300 kcmil THHN in other 6" conduit

ConduitInside areaMost 300 kcmil THHN
Rigid metal conduit (RMC, GRC)29.15825
Rigid PVC conduit, Schedule 4028.56724
Rigid PVC conduit, Schedule 8025.59822

300 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 6" PVC Sch 40

Charts