ConduitCount

How many 250 kcmil THHN fit in 6" PVC Sch 40?

28250 kcmil THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 40

28.567 sq in × 40 % = 11.4268 sq in allowed. ÷ 0.3970 sq in per wire = 28.78, so 28.

28 250 kcmil THHN in 6" PVC Sch 40, drawn to scale

This pull in numbers

28 wires fill
38.9 % of 6" PVC Sch 40
Limit for three or more
40 %
For 29 or more
no bigger PVC Sch 40
Pipe to wire diameter
8.48 to 1
In THW insulation
25 fit
In XHHW-2 insulation
29 fit

Before you pull 28

250 kcmil THHN in other 6" conduit

ConduitInside areaMost 250 kcmil THHN
Rigid metal conduit (RMC, GRC)29.15829
Rigid PVC conduit, Schedule 4028.56728
Rigid PVC conduit, Schedule 8025.59825

250 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 6" PVC Sch 40

Charts