How many #1 THHN fit in 6" PVC Sch 40?
731 AWG THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 40
28.567 sq in × 40 % = 11.4268 sq in allowed. ÷ 0.1562 sq in per wire = 73.15, so 73.
This pull in numbers
- 73 wires fill
- 39.9 % of 6" PVC Sch 40
- Limit for three or more
- 40 %
- For 74 or more
- no bigger PVC Sch 40
- Pipe to wire diameter
- 13.52 to 1
- In THW insulation
- 60 fit
- In XHHW-2 insulation
- 74 fit
Before you pull 73
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 73 is the total, not the hots.
- Derating. If all 73 were current-carrying, each would be adjusted to 35 % of its ampacity (Table 310.15(C)(1)): a #1 THHN at 145 A in the 90 °C column becomes 50.8 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#1 THHN in other 6" conduit
| Conduit | Inside area | Most #1 THHN |
|---|---|---|
| Rigid metal conduit (RMC, GRC) | 29.158 | 74 |
| Rigid PVC conduit, Schedule 40 | 28.567 | 73 |
| Rigid PVC conduit, Schedule 80 | 25.598 | 65 |
#1 THHN in other PVC Sch 40 sizes
Other wire sizes in 6" PVC Sch 40
#4: 138#3: 117#2: 98#1: 73#1/0: 61#2/0: 51#3/0: 42#4/0: 35250 kcmil: 28300 kcmil: 24350 kcmil: 21500 kcmil: 16