ConduitCount

6" PVC Sch 80 conduit fill

6" Rigid PVC conduit, Schedule 80 has an inside area of 25.598 sq in (5.709 in across). Three or more wires may take 40 % of it: 10.2392 sq in.

One wire, 53 %
13.5669 sq in
Two wires, 31 %
7.9354 sq in
Three or more, 40 %
10.2392 sq in
Nipple, 60 %
15.3588 sq in
Support
Every 8 ft, 3 ft from boxes
Sold in
10 ft sticks
55 #1/0 THHN, the most it may hold, drawn to scale

How many wires fit in 6" PVC Sch 80

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG1055736736
12 AWG770565565
10 AWG485421421
8 AWG279234234
6 AWG202173141
4 AWG124125105
3 AWG10510690
2 AWG888977
1 AWG656654
1/0 AWG555646
2/0 AWG464639
3/0 AWG383833
4/0 AWG313227
250 kcmil252622
300 kcmil222219
350 kcmil192017
400 kcmil171715
500 kcmil141413
600 kcmil121110
700 kcmil10109
750 kcmil998
800 kcmil998
900 kcmil887
1000 kcmil777

Other 6" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 8025.5981055770485279202
Rigid metal conduit (RMC, GRC)29.1581202877552318230
Rigid PVC conduit, Schedule 4028.5671178859541312225

About PVC Sch 80

Schedule 80 has a thicker wall for where it can be hit, so it holds fewer wires than Schedule 40 of the same trade size. Support is the same as Schedule 40 (Table 352.30). See strap spacing and the fill rules.