ConduitCount

How many #4/0 THHN fit in 6" PVC Sch 40?

354/0 AWG THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 40

28.567 sq in × 40 % = 11.4268 sq in allowed. ÷ 0.3237 sq in per wire = 35.30, so 35.

35 #4/0 THHN in 6" PVC Sch 40, drawn to scale

This pull in numbers

35 wires fill
39.7 % of 6" PVC Sch 40
Limit for three or more
40 %
For 36 or more
no bigger PVC Sch 40
Pipe to wire diameter
9.39 to 1
In THW insulation
30 fit
In XHHW-2 insulation
35 fit

Before you pull 35

#4/0 THHN in other 6" conduit

ConduitInside areaMost #4/0 THHN
Rigid metal conduit (RMC, GRC)29.15836
Rigid PVC conduit, Schedule 4028.56735
Rigid PVC conduit, Schedule 8025.59831

#4/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 6" PVC Sch 40

Charts