How many #1/0 THHN fit in 1-1/4" PVC Sch 80?

21/0 AWG THHN/THWN-2 wires in 1-1/4" Rigid PVC conduit, Schedule 80

1.237 sq in × 31 % = 0.3835 sq in allowed. ÷ 0.1855 sq in per wire = 2.07.

2 #1/0 THHN in 1-1/4" PVC Sch 80, drawn to scale

This pull in numbers

2 wires fill
30.0 % of 1-1/4" PVC Sch 80
Limit for two
31 %
For 3 or more
1-1/2" PVC Sch 80, up to 3
Pipe to wire diameter
2.58 to 1
In THW insulation
1 fit
In XHHW-2 insulation
2 fit

Before you pull 2

#1/0 THHN in other 1-1/4" conduit

#1/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 1-1/4" PVC Sch 80

Charts