How many #1 THHN fit in 1-1/4" PVC Sch 80?

31 AWG THHN/THWN-2 wires in 1-1/4" Rigid PVC conduit, Schedule 80

1.237 sq in × 40 % = 0.4948 sq in allowed. ÷ 0.1562 sq in per wire = 3.17, so 3.

3 #1 THHN in 1-1/4" PVC Sch 80, drawn to scale

This pull in numbers

3 wires fill
37.9 % of 1-1/4" PVC Sch 80
Limit for three or more
40 %
For 4 or more
1-1/2" PVC Sch 80, up to 4
Pipe to wire diameter
2.81 to 1
In THW insulation
2 fit
In XHHW-2 insulation
3 fit

The pipe is 2.81 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 3

#1 THHN in other 1-1/4" conduit

#1 THHN in other PVC Sch 80 sizes