ConduitCount

How many #14 THHN fit in 1-1/4" PVC Sch 80?

5114 AWG THHN/THWN-2 wires in 1-1/4" Rigid PVC conduit, Schedule 80

1.237 sq in × 40 % = 0.4948 sq in allowed. ÷ 0.0097 sq in per wire = 51.01, so 51.

51 #14 THHN in 1-1/4" PVC Sch 80, drawn to scale

This pull in numbers

51 wires fill
40.0 % of 1-1/4" PVC Sch 80
Limit for three or more
40 %
For 52 or more
1-1/2" PVC Sch 80, up to 70
Pipe to wire diameter
11.31 to 1
In THW insulation
35 fit
In XHHW-2 insulation
35 fit

Before you pull 51

#14 THHN in other 1-1/4" conduit

#14 THHN in other PVC Sch 80 sizes

Other wire sizes in 1-1/4" PVC Sch 80

Charts