ConduitCount

How many #1 THHN fit in 1-1/4" IMC?

41 AWG THHN/THWN-2 wires in 1-1/4" Intermediate metal conduit

1.647 sq in × 40 % = 0.6588 sq in allowed. ÷ 0.1562 sq in per wire = 4.22, so 4.

4 #1 THHN in 1-1/4" IMC, drawn to scale

This pull in numbers

4 wires fill
37.9 % of 1-1/4" IMC
Limit for three or more
40 %
For 5 or more
1-1/2" IMC, up to 5
Pipe to wire diameter
3.25 to 1
In THW insulation
3 fit
In XHHW-2 insulation
4 fit

Before you pull 4

#1 THHN in other 1-1/4" conduit

#1 THHN in other IMC sizes

Other wire sizes in 1-1/4" IMC

Charts