How many #1 THHN fit in 1-1/4" Rigid?

41 AWG THHN/THWN-2 wires in 1-1/4" Rigid metal conduit (RMC, GRC)

1.526 sq in × 40 % = 0.6104 sq in allowed. ÷ 0.1562 sq in per wire = 3.91, which Note 7 rounds up to 4 because the decimal is 0.8 or more.

4 #1 THHN in 1-1/4" Rigid, drawn to scale

This pull in numbers

4 wires fill
40.9 % of 1-1/4" Rigid
Limit for three or more
40 %
For 5 or more
1-1/2" Rigid, up to 5
Pipe to wire diameter
3.13 to 1
In THW insulation
3 fit
In XHHW-2 insulation
4 fit

The pipe is 3.13 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 4