ConduitCount

How many #10 THHN fit in 2" EMT?

6310 AWG THHN/THWN-2 wires in 2" Electrical metallic tubing

3.356 sq in × 40 % = 1.3424 sq in allowed. ÷ 0.0211 sq in per wire = 63.62, so 63.

63 #10 THHN in 2" EMT, drawn to scale

This pull in numbers

63 wires fill
39.6 % of 2" EMT
Limit for three or more
40 %
For 64 or more
2-1/2" EMT, up to 111
Pipe to wire diameter
12.60 to 1
In THW insulation
55 fit
In XHHW-2 insulation
55 fit

Before you pull 63

#10 THHN in other 2" conduit

#10 THHN in other EMT sizes

Other wire sizes in 2" EMT

Charts