ConduitCount

How many #10 THHN fit in 1-1/2" EMT?

3810 AWG THHN/THWN-2 wires in 1-1/2" Electrical metallic tubing

2.036 sq in × 40 % = 0.8144 sq in allowed. ÷ 0.0211 sq in per wire = 38.60, so 38.

38 #10 THHN in 1-1/2" EMT, drawn to scale

This pull in numbers

38 wires fill
39.4 % of 1-1/2" EMT
Limit for three or more
40 %
For 39 or more
2" EMT, up to 63
Pipe to wire diameter
9.82 to 1
In THW insulation
33 fit
In XHHW-2 insulation
33 fit

Before you pull 38

#10 THHN in other 1-1/2" conduit

#10 THHN in other EMT sizes

Other wire sizes in 1-1/2" EMT

Charts