610 AWG THHN/THWN-2 wires in 1/2" Intermediate metal conduit

0.342 sq in × 40 % = 0.1368 sq in allowed. ÷ 0.0211 sq in per wire = 6.48, so 6.

6 #10 THHN in 1/2" IMC, drawn to scale

This pull in numbers

6 wires fill
37.0 % of 1/2" IMC
Limit for three or more
40 %
For 7 or more
3/4" IMC, up to 11
Pipe to wire diameter
4.02 to 1
In THW insulation
5 fit
In XHHW-2 insulation
5 fit