6212 AWG THHN/THWN-2 wires in 1-1/2" Rigid metal conduit (RMC, GRC)

2.071 sq in × 40 % = 0.8284 sq in allowed. ÷ 0.0133 sq in per wire = 62.29, so 62.

62 #12 THHN in 1-1/2" Rigid, drawn to scale

This pull in numbers

62 wires fill
39.8 % of 1-1/2" Rigid
Limit for three or more
40 %
For 63 or more
2" Rigid, up to 102
Pipe to wire diameter
12.49 to 1
In THW insulation
45 fit
In XHHW-2 insulation
45 fit

Before you pull 62

#12 THHN in other 1-1/2" conduit

#12 THHN in other Rigid sizes

Other wire sizes in 1-1/2" Rigid