How many #14 THHN fit in 1" IMC?
3914 AWG THHN/THWN-2 wires in 1" Intermediate metal conduit
0.959 sq in × 40 % = 0.3836 sq in allowed. ÷ 0.0097 sq in per wire = 39.55, so 39.
This pull in numbers
- 39 wires fill
- 39.4 % of 1" IMC
- Limit for three or more
- 40 %
- For 40 or more
- 1-1/4" IMC, up to 68
- Pipe to wire diameter
- 9.95 to 1
- In THW insulation
- 27 fit
- In XHHW-2 insulation
- 27 fit
Before you pull 39
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 39 is the total, not the hots.
- Derating. If all 39 were current-carrying, each would be adjusted to 40 % of its ampacity (Table 310.15(C)(1)): a #14 THHN at 25 A in the 90 °C column becomes 10 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#14 THHN in other 1" conduit
| Conduit | Inside area | Most #14 THHN |
|---|---|---|
| Electrical metallic tubing | 0.864 | 35 |
| Intermediate metal conduit | 0.959 | 39 |
| Rigid metal conduit (RMC, GRC) | 0.887 | 36 |
| Rigid PVC conduit, Schedule 40 | 0.832 | 34 |
| Rigid PVC conduit, Schedule 80 | 0.688 | 28 |
| Flexible metal conduit (FMC, Greenfield) | 0.817 | 33 |
| Liquidtight flexible metal conduit (LFMC) | 0.873 | 36 |
| Electrical nonmetallic tubing (smurf tube) | 0.832 | 34 |
#14 THHN in other IMC sizes
Other wire sizes in 1" IMC
#14: 39#12: 29#10: 18#8: 10#6: 7#4: 4#3: 4#2: 3#1: 1#1/0: 1#2/0: 1#3/0: 1#4/0: 1250 kcmil: 1300 kcmil: 1