ConduitCount

How many #14 THHN fit in 1-1/2" IMC?

9114 AWG THHN/THWN-2 wires in 1-1/2" Intermediate metal conduit

2.225 sq in × 40 % = 0.8900 sq in allowed. ÷ 0.0097 sq in per wire = 91.75, so 91.

91 #14 THHN in 1-1/2" IMC, drawn to scale

This pull in numbers

91 wires fill
39.7 % of 1-1/2" IMC
Limit for three or more
40 %
For 92 or more
2" IMC, up to 149
Pipe to wire diameter
15.16 to 1
In THW insulation
64 fit
In XHHW-2 insulation
64 fit

Before you pull 91

#14 THHN in other 1-1/2" conduit

#14 THHN in other IMC sizes

Other wire sizes in 1-1/2" IMC

Charts