14/0 AWG THHN/THWN-2 wires in 1" Intermediate metal conduit

0.959 sq in × 53 % = 0.5083 sq in allowed. ÷ 0.3237 sq in per wire = 1.57.

1 #4/0 THHN in 1" IMC, drawn to scale

This pull in numbers

1 wires fill
33.8 % of 1" IMC
Limit for one
53 %
For 2 or more
1-1/2" IMC, up to 2
Pipe to wire diameter
1.72 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

#4/0 THHN in other 1" conduit

#4/0 THHN in other IMC sizes

Other wire sizes in 1" IMC