ConduitCount

How many #2/0 THHN fit in 1-1/4" IMC?

32/0 AWG THHN/THWN-2 wires in 1-1/4" Intermediate metal conduit

1.647 sq in × 40 % = 0.6588 sq in allowed. ÷ 0.2223 sq in per wire = 2.96, which Note 7 rounds up to 3 because the decimal is 0.8 or more.

3 #2/0 THHN in 1-1/4" IMC, drawn to scale

This pull in numbers

3 wires fill
40.5 % of 1-1/4" IMC
Limit for three or more
40 %
For 4 or more
1-1/2" IMC, up to 4
Pipe to wire diameter
2.72 to 1
In THW insulation
1 fit
In XHHW-2 insulation
3 fit

Before you pull 3

#2/0 THHN in other 1-1/4" conduit

#2/0 THHN in other IMC sizes

Other wire sizes in 1-1/4" IMC

Charts