ConduitCount

How many #2/0 THHN fit in 4" IMC?

242/0 AWG THHN/THWN-2 wires in 4" Intermediate metal conduit

13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.2223 sq in per wire = 24.53, so 24.

24 #2/0 THHN in 4" IMC, drawn to scale

This pull in numbers

24 wires fill
39.1 % of 4" IMC
Limit for three or more
40 %
For 25 or more
no bigger IMC
Pipe to wire diameter
7.83 to 1
In THW insulation
20 fit
In XHHW-2 insulation
25 fit

Before you pull 24

#2/0 THHN in other 4" conduit

#2/0 THHN in other IMC sizes

Other wire sizes in 4" IMC

Charts