How many #2/0 THHN fit in 2-1/2" IMC?
92/0 AWG THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit
5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.2223 sq in per wire = 9.24, so 9.
This pull in numbers
- 9 wires fill
- 39.0 % of 2-1/2" IMC
- Limit for three or more
- 40 %
- For 10 or more
- 3" IMC, up to 14
- Pipe to wire diameter
- 4.81 to 1
- In THW insulation
- 8 fit
- In XHHW-2 insulation
- 9 fit
Before you pull 9
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 9 is the total, not the hots.
- Derating. If all 9 were current-carrying, each would be adjusted to 70 % of its ampacity (Table 310.15(C)(1)): a #2/0 THHN at 195 A in the 90 °C column becomes 136.5 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#2/0 THHN in other 2-1/2" conduit
| Conduit | Inside area | Most #2/0 THHN |
|---|---|---|
| Electrical metallic tubing | 5.858 | 10 |
| Intermediate metal conduit | 5.135 | 9 |
| Rigid metal conduit (RMC, GRC) | 4.866 | 8 |
| Rigid PVC conduit, Schedule 40 | 4.695 | 8 |
| Rigid PVC conduit, Schedule 80 | 4.119 | 7 |
| Flexible metal conduit (FMC, Greenfield) | 4.909 | 9 |
| Liquidtight flexible metal conduit (LFMC) | 4.881 | 8 |
#2/0 THHN in other IMC sizes
Other wire sizes in 2-1/2" IMC
#12: 154#10: 97#8: 56#6: 40#4: 25#3: 21#2: 17#1: 13#1/0: 11#2/0: 9#3/0: 7#4/0: 6250 kcmil: 5300 kcmil: 4350 kcmil: 4500 kcmil: 3