ConduitCount

How many #3 THHN fit in 1-1/4" IMC?

63 AWG THHN/THWN-2 wires in 1-1/4" Intermediate metal conduit

1.647 sq in × 40 % = 0.6588 sq in allowed. ÷ 0.0973 sq in per wire = 6.77, so 6.

6 #3 THHN in 1-1/4" IMC, drawn to scale

This pull in numbers

6 wires fill
35.4 % of 1-1/4" IMC
Limit for three or more
40 %
For 7 or more
1-1/2" IMC, up to 9
Pipe to wire diameter
4.11 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 6

#3 THHN in other 1-1/4" conduit

#3 THHN in other IMC sizes

Other wire sizes in 1-1/4" IMC

Charts