ConduitCount

How many #6 THHN fit in 1-1/4" IMC?

136 AWG THHN/THWN-2 wires in 1-1/4" Intermediate metal conduit

1.647 sq in × 40 % = 0.6588 sq in allowed. ÷ 0.0507 sq in per wire = 12.99, which Note 7 rounds up to 13 because the decimal is 0.8 or more.

13 #6 THHN in 1-1/4" IMC, drawn to scale

This pull in numbers

13 wires fill
40.0 % of 1-1/4" IMC
Limit for three or more
40 %
For 14 or more
1-1/2" IMC, up to 17
Pipe to wire diameter
5.70 to 1
In THW insulation
9 fit
In XHHW-2 insulation
11 fit

Before you pull 13

#6 THHN in other 1-1/4" conduit

#6 THHN in other IMC sizes

Other wire sizes in 1-1/4" IMC

Charts