How many #4 THHN fit in 1-1/4" IMC?

84 AWG THHN/THWN-2 wires in 1-1/4" Intermediate metal conduit

1.647 sq in × 40 % = 0.6588 sq in allowed. ÷ 0.0824 sq in per wire = 8.00, which Note 7 rounds up to 8 because the decimal is 0.8 or more.

8 #4 THHN in 1-1/4" IMC, drawn to scale

This pull in numbers

8 wires fill
40.0 % of 1-1/4" IMC
Limit for three or more
40 %
For 9 or more
1-1/2" IMC, up to 11
Pipe to wire diameter
4.47 to 1
In THW insulation
6 fit
In XHHW-2 insulation
8 fit

Before you pull 8

#4 THHN in other 1-1/4" conduit

#4 THHN in other IMC sizes

Other wire sizes in 1-1/4" IMC