ConduitCount

How many #2/0 THHN fit in 2" IMC?

62/0 AWG THHN/THWN-2 wires in 2" Intermediate metal conduit

3.630 sq in × 40 % = 1.4520 sq in allowed. ÷ 0.2223 sq in per wire = 6.53, so 6.

6 #2/0 THHN in 2" IMC, drawn to scale

This pull in numbers

6 wires fill
36.7 % of 2" IMC
Limit for three or more
40 %
For 7 or more
2-1/2" IMC, up to 9
Pipe to wire diameter
4.04 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit

Before you pull 6

#2/0 THHN in other 2" conduit

#2/0 THHN in other IMC sizes

Other wire sizes in 2" IMC

Charts