ConduitCount

How many #2/0 THHN fit in 4" EMT?

262/0 AWG THHN/THWN-2 wires in 4" Electrical metallic tubing

14.753 sq in × 40 % = 5.9012 sq in allowed. ÷ 0.2223 sq in per wire = 26.55, so 26.

26 #2/0 THHN in 4" EMT, drawn to scale

This pull in numbers

26 wires fill
39.2 % of 4" EMT
Limit for three or more
40 %
For 27 or more
no bigger EMT
Pipe to wire diameter
8.15 to 1
In THW insulation
22 fit
In XHHW-2 insulation
27 fit

Before you pull 26

#2/0 THHN in other 4" conduit

#2/0 THHN in other EMT sizes

Other wire sizes in 4" EMT

Charts