393 AWG THHN/THWN-2 wires in 3-1/2" Flexible metal conduit (FMC, Greenfield)

9.621 sq in × 40 % = 3.8484 sq in allowed. ÷ 0.0973 sq in per wire = 39.55, so 39.

39 #3 THHN in 3-1/2" Flex, drawn to scale

This pull in numbers

39 wires fill
39.4 % of 3-1/2" Flex
Limit for three or more
40 %
For 40 or more
4" Flex, up to 51
Pipe to wire diameter
9.94 to 1
In THW insulation
34 fit
In XHHW-2 insulation
40 fit

Before you pull 39

#3 THHN in other 3-1/2" conduit

ConduitInside areaMost #3 THHN
Electrical metallic tubing11.54547
Intermediate metal conduit10.58443
Rigid metal conduit (RMC, GRC)10.01041
Rigid PVC conduit, Schedule 409.73740
Rigid PVC conduit, Schedule 808.68835
Flexible metal conduit (FMC, Greenfield)9.62139
Liquidtight flexible metal conduit (LFMC)9.73140

#3 THHN in other Flex sizes