ConduitCount

How many #2/0 THHN fit in 3-1/2" PVC Sch 80?

152/0 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 80

8.688 sq in × 40 % = 3.4752 sq in allowed. ÷ 0.2223 sq in per wire = 15.63, so 15.

15 #2/0 THHN in 3-1/2" PVC Sch 80, drawn to scale

This pull in numbers

15 wires fill
38.4 % of 3-1/2" PVC Sch 80
Limit for three or more
40 %
For 16 or more
4" PVC Sch 80, up to 20
Pipe to wire diameter
6.25 to 1
In THW insulation
13 fit
In XHHW-2 insulation
16 fit

Before you pull 15

#2/0 THHN in other 3-1/2" conduit

#2/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 3-1/2" PVC Sch 80

Charts