ConduitCount

How many 500 kcmil THHN fit in 3-1/2" Flex?

5500 kcmil THHN/THWN-2 wires in 3-1/2" Flexible metal conduit (FMC, Greenfield)

9.621 sq in × 40 % = 3.8484 sq in allowed. ÷ 0.7073 sq in per wire = 5.44, so 5.

5 500 kcmil THHN in 3-1/2" Flex, drawn to scale

This pull in numbers

5 wires fill
36.8 % of 3-1/2" Flex
Limit for three or more
40 %
For 6 or more
4" Flex, up to 7
Pipe to wire diameter
3.69 to 1
In THW insulation
5 fit
In XHHW-2 insulation
5 fit

Before you pull 5

500 kcmil THHN in other 3-1/2" conduit

ConduitInside areaMost 500 kcmil THHN
Electrical metallic tubing11.5456
Intermediate metal conduit10.5846
Rigid metal conduit (RMC, GRC)10.0105
Rigid PVC conduit, Schedule 409.7375
Rigid PVC conduit, Schedule 808.6885
Flexible metal conduit (FMC, Greenfield)9.6215
Liquidtight flexible metal conduit (LFMC)9.7315

500 kcmil THHN in other Flex sizes

Other wire sizes in 3-1/2" Flex

Charts